Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR.One conductor is manufactured with an extruded ridge for phase identification.
2.The Specifications of ACSR conductor
Conductor: Copper or Aluminium
Insulation: XLPE
Normally,ABC Cable(ABC Bundled Cable-Aerial Cable) do not use copper,because Aluminium Cost is high,most of our customers use aluminium.
Cable Standards:
Chinese National Standards, IEC,SANS 1418-1, SANS1418-2, ASTMB230, ASTMB231,ASTM B398,ASTM B399, NF C33-209 and etc. upon request.
Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1
Table 01 Aerial Bundled Cable-ABC-BS 7870-5
ABC Cables without Street Lighting | |||||||
1+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Completed Cable | |||||
Section | Insulation Thickness | Electrical Resistance | Section | Insulation Thickness | Electrical Resistance | Overall Diameter | Cable Weight |
DC.20°C | DC.20°C | ||||||
No.xmm2 | mm | Ω/km | mm2 | mm | Ω/km | mm | kg/km |
1x25 | 1.3 | 1.20 | 25 | 1.3 | 1.20 | 17.6 | 210 |
1x35 | 1.3 | 0.868 | 35 | 1.3 | 0.868 | 19.6 | 270 |
1x50 | 1.5 | 0.641 | 50 | 1.5 | 0.641 | 23 | 360 |
1x70 | 1.5 | 0.443 | 70 | 1.5 | 0.443 | 26.4 | 500 |
1x95 | 1.7 | 0.320 | 95 | 1.7 | 0.320 | 30.6 | 680 |
3+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Completed Cable | |||||
Section | Insulation Thickness | Electrical Resistance | Section | Insulation Thickness | Electrical Resistance | Overall Diameter | Cable Weight |
DC.20°C | DC.20°C | ||||||
No.xmm2 | mm | Ω/km | mm2 | mm | Ω/km | mm | kg/km |
3x25 | 1.3 | 1.20 | 25 | 1.3 | 1.20 | 21.2 | 410 |
3x35 | 1.3 | 0.868 | 35 | 1.3 | 0.868 | 23.7 | 550 |
3x50 | 1.5 | 0.641 | 50 | 1.5 | 0.641 | 27.8 | 730 |
3x70 | 1.5 | 0.443 | 70 | 1.5 | 0.443 | 31.9 | 1000 |
3x95 | 1.7 | 0.320 | 95 | 1.7 | 0.320 | 36.9 | 1370 |
3x120 | 1.7 | 0.253 | 120 | 1.7 | 0.253 | 40.6 | 1690 |
ABC Cables with Street Lighting | |||||||
3+1+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Street Lighting Conductor | Completed Cable | ||||
Section | Insulation Thickness | Section | Insulation Thickness | Section | Insulation Thickness | Overall Diameter | Cable Weight |
No.xmm2 | mm | mm2 | mm | mm2 | mm | mm | kg/km |
3x50 | 1.5 | 50 | 1.5 | 25 | 1.3 | 29.8 | 830 |
3x70 | 1.5 | 70 | 1.5 | 25 | 1.3 | 33.6 | 1100 |
3x95 | 1.7 | 95 | 1.7 | 25 | 1.3 | 38.2 | 1470 |